Set Endian Architecture

 

Modbus follows the Big Endian byte ordering system. Therefore the byte ordering has to be reversed if the Modbus library is deployed on a Little Endian processor. The library has a macro ENDIAN_STYLE, used to set the correct Endian characteristic.

 

Steps

a)   Open file MSPL_UserIf.h


b)   Locate the definition of macro ENDIAN_STYLE


c)    If your platform is Little Endian, change the above macro's value to LITTLE_ENDIAN. If it is Big Endian, change the macro's value to BIG_ENDIAN. The modified line should look like this:

#define ENDIAN_STYLE LITTLE_ENDIAN/* for Little Endian */

#define ENDIAN_STYLE BIG_ENDIAN/* for Big Endian */


d)   Rebuild your project and test.

 

Notes

  • The utility functions provided by the Formatter (e.g. MSPL_ShortIntsToBuffer) are "Endian-aware" - they are programmed check and ensure that transfers from
    interpreted data types to raw buffers conform to Endianess of the platform.

  • If you use your own code for such transfers, remember to address the issue of Endianess. Raw data in a Modbus packet is always in Big Endian format.

  • To know the Endianess of your platform, refer to the User Manual of your processor.

  • If you are unsure of the Endianess of your platform, a simple technique to determine this is to create a 'C' program with an unsigned short int variable (16-bit)
    and store the value 0xABCD in it:

     

    unsigned short int testVar = 0xABCD;

     

    Then debug this program and see the memory contents (using a Memory Dump or Memory Watch window) at the location of this variable. If you find 0xAB stored first and then 0xCD, you have a Big Endian system, else you have a Small Endian system.

  •  